Universal AC input/full range
Small volume, low weight, high efficiency
Protections: Short circuit/over load/over voltage
Cooling by free air convection
Can be installed on Din-Rail: TS-35/7.5 or TS-35/15
100% full load burn-in test
2 year warranty
| Model |
|
DR-75-12 |
DR-75-24 |
DR-75-48 |
| Output |
DC output Voltage |
12V |
24V |
48V |
| Voltage tolerance |
±1.0% |
±1.0% |
±1.0% |
| Rated Current |
6.3A |
3.2A |
1.6A |
| Related Power |
75w |
75w |
75w |
| Wave&Noise |
100mVp-p |
150mVp-p |
240mVp-p |
| Adjustable range for DC Voltage |
±10% |
±10% |
±10% |
| Set up,rise,hold up time |
800ms 600ms 50ms |
| Input |
Voltage Range |
85 ~ 264VAC 47-63HZ 120-370VDC |
| Input Current |
4A/115VAC 0.5A/230VAC |
| Efficiency |
77% |
77% |
82% |
| AC inrush current |
Cold start current 15A/115V 30A /230VAC |
| Leakage current |
<0.5mA/240VAC |
| Protection |
Overload |
Related output power 105-135% start overload protection |
| Protection type: cutoff output, recovery after restart power |
| Over voltage |
13.8V-16.2V |
27.6V-32.4V |
55.2V-64.8V |
| Hiccup mode,recovers automatically after fault condition |
| Environment |
Working temp humidity |
-10~+60°C 20%~90%RH |
| Stor temp, humidity |
-20~+85°C 20%~90%RH Non-condensing |
| Safety |
Withstand voltage |
I/P-O/P:1.5KVAC 1min |
| I/P-FG:1.5KVAC 1min |
| O/P-FG:0.5KVAC 1min |
| Standard |
Safety standard |
Fit UL1012 |
| Refer |
Design refer to GB4943,UL60950,EN60950 |
| EMC standard |
Design refer to GB9254,EN55022 Class A |
| Size |
size |
L100*W56*H125mm |
| Package |
0.55kg, 40 pcs/22kg |