Customization: | Available |
---|---|
Output Type: | Single |
Warranty: | >2 Years |
Still deciding? Get samples of US$ 88/Piece
Request Sample
|
Suppliers with verified business licenses
Audited by an independent third-party inspection agency
MODEL |
RSP-1000-12 |
RSP-1000-15 |
RSP-1000-24 |
RSP-1000-27 |
RSP-1000-48 |
|
OUTPUT |
DC VOLTAGE |
12V |
15V |
24V |
27V |
48V |
CURRENT RANGE |
0 ~75A |
0 ~ 50A |
0 ~ 40A |
0 ~ 37A |
0 ~ 21A |
|
RATED CURRENT |
75A |
50A |
40A |
37A |
21A |
|
RATED POWER |
900W |
750W |
960W |
999W |
1008W |
|
RIPPLE & NOISE (max.) |
150mVp-p |
150mVp-p |
150mVp-p |
150mVp-p |
150mVp-p |
|
VOLTAGE ADJ. RANGE |
10 ~ 13.5V |
13.5~16.5V |
20 ~ 26.4V |
24 ~ 30V |
43 ~ 55V |
|
VOLTAGE TOLERANCE |
1.0% |
|||||
LINE REGULATION |
0.5% |
|||||
LOAD REGULATION |
0.5% |
|||||
SETUP RISE TIME |
300ms, 50ms at full load |
|||||
HOLD UP TIME |
16ms/230VAC 16ms/115VAC at full load |
|||||
INPUT |
VOLTAGE RANGE |
90 ~ 264VAC 127 ~ 370VDC |
||||
FREQUENCY RANGE |
47 ~ 63Hz |
|||||
POWER FACTOR |
0.95/230VAC 0.98/115VAC at full load |
|||||
EFFICIENCY |
83% |
85% |
88% |
88% |
90% |
|
AC CURRENT |
12A/115VAC 6A/230VAC |
|||||
INRUSH CURRENT |
25A/115VAC 40A/230VAC |
|||||
LEAKAGE CURRENT |
<2mA / 240VAC |
|||||
PROTECTION |
OVER LOAD |
105 ~ 125% rated output power |
||||
Protection type : Constant current limiting, recovers automatically after fault condition is removed |
||||||
OVER VOLTAGE |
13.8~16.8V |
17 ~ 20.5V |
27.6 ~ 32.4V |
31 ~ 36.5V |
56.6 ~ 66.2V |
|
Protection type : Shut down o/p voltage, re-power to recover |
||||||
OVER TEMP |
85oC 5 (TSW2 ) detect on heatsink of O/P diode; 75oC 5 (TSW1 ) detect on heatsink of power transistor |
|||||
Protection type : Shut down o/p voltage, recovers automatically after temperature goes down |
||||||
AUXILIARY POWER |
5V @ 0.5A (+5%, -8%) |
|||||
REMOTE CONTROL |
Note.6 Power on : short between on/off(pin6) & -S(pin2) on CN50 Power off : open between on/off(pin6) & -S(pin2) on CN50 |
|||||
FUNCTION |
DC-OK SIGNAL |
The TTL signal out, PSU turn on = 3.3 ~ 5.6V ; PSU turn off = 0 ~ 1V |
||||
OUTPUT VOLTAGE TRIM Note.6 |
Adjustment of output voltage is possible between 40 ~ 110% of rated output |
|||||
CURRENT SHARING |
Please refer to function manual |
|||||
ENVIRONMENT |
WORKING TEMP. |
-20 ~ +60oC (Refer to output load derating curve) |
||||
WORKING HUMIDITY |
20 ~ 90% RH non-condensing |
|||||
STORAGE TEMP., HUMIDITY |
-40 ~ +85oC, 10 ~ 95% RH |
|||||
TEMP. COEFFICIENT |
0.02%/oC (0 ~ 60oC ) |
|||||
VIBRATION |
10 ~ 500Hz, 2G 10min./1cycle, period for 60min. each along X, Y, Z axes |
|||||
SAFETY &EMC |
SAFETY STANDARDS |
UL60950-1, TUV EN60950-1 approved |
||||
WITHSTAND VOLTAGE |
I/P-O/P:3KVAC I/P-FG:1.5KVAC O/P-FG:0.5KVAC |
|||||
ISOLATION RESISTANCE |
I/P-O/P, I/P-FG, O/P-FG:100M Ohms/500VDC |
|||||
EMI CONDUCTION & RADIATION |
Compliance to EN55022 (CISPR22) |
|||||
HARMONIC CURRENT |
Compliance to EN61000-3-2,EN61000-3-3 |
|||||
EMS IMMUNITY |
Compliance to EN61000-4-2,3,4,5,6,8,11; ENV50204, EN55024, EN61000-6-2, EN61204-3, heavy industry level, criteria A |
|||||
OTHERS |
MTBF |
35K hrs min. MIL-HDBK-217F (25 ) |
||||
DIMENSION |
268*130*40mm (L*W*H) |
|||||
PACKING |
1.4Kg; 6pcs/12.7Kg/0.99CUFT |