MODEL |
NDR-75-12 |
NDR-75-24 |
NDR-75-48 |
DC VOLTAGE |
12V |
24V |
48V |
RATED CURRENT |
6.3A |
3.2A |
1.6A |
CURRENT RANGE |
0 ~ 6.3A |
0 ~ 3.2A |
0 ~ 1.6A |
RATED POWER |
75.6W |
76.8W |
76.8W |
RIPPLE & NOISE (max.) Note.2 |
80mVp-p |
120mVp-p |
150mVp-p |
VOLTAGE ADJ. RANGE |
12 ~ 14V |
24 ~ 28V |
48 ~ 55V |
VOLTAGE TOLERANCE Note.3 |
±2.0% |
±1.0% |
±1.0% |
LINE REGULATION |
±0.5% |
±0.5% |
±0.5% |
LOAD REGULATION |
±1.0% |
±1.0% |
±1.0% |
SETUP, RISE TIME |
1200ms, 60ms/230VAC 2000ms, 60ms/115VAC at full load |
HOLD UP TIME (Typ.) |
60ms/230VAC 12ms/115VAC at full load |
VOLTAGE RANGE Note.6 |
90 ~ 264VAC 127 ~ 370VDC [DC input operation possible by connecting AC/L(+), AC/N(-)] |
FREQUENCY RANGE |
47 ~ 63Hz |
EFFICIENCY (Typ.) |
85.50% |
88% |
89% |
AC CURRENT (Typ.) |
1.45A/115VAC 0.9A/230VAC |
INRUSH CURRENT (Typ.) |
20A/115VAC 35A/230VAC |
LEAKAGE CURRENT |
<1mA / 240VAC |
OVERLOAD |
105 ~ 130% rated output power |
Protection type : Constant current limiting, recovers automatically after fault condition is removed |
OVER VOLTAGE |
14 ~ 17V |
29 ~ 33V |
56 ~ 65V |
Protection type : Shut down o/p voltage, re-power on to recover |
OVER TEMPERATURE |
Protection type : Shut down o/p voltage, re-power on to recover |
WORKING TEMP. |
-20 ~ +70ºC (Refer to "Derating Curve") |
WORKING HUMIDITY |
20 ~ 95% RH non-condensing |
STORAGE TEMP., HUMIDITY |
-40 ~ +85ºC, 10 ~ 95% RH |
TEMP. COEFFICIENT |
±0.03%/ºC (0 ~ 50ºC) |
VIBRATION |
Component:10 ~ 500Hz, 2G 10min./1cycle, 60min. each along X, Y, Z axes; Mounting: Compliance to IEC60068-2-6 |
SAFETY STANDARDS |
UL508, TUV EN62368-1, EAC TP TC 004 approved;(meet EN60204-1) |
WITHSTAND VOLTAGE |
I/P-O/P:3KVAC I/P-FG:2KVAC O/P-FG:0.5KVAC |
ISOLATION RESISTANCE |
I/P-O/P, I/P-FG, O/P-FG:>100M Ohms / 500VDC / 25ºC/ 70% RH |
EMC EMISSION |
Compliance to EN55032 (CISPR32), EN61204-3 Class B, EN61000-3-2,-3, EAC TP TC 020 |
EMC IMMUNITY |
Compliance to EN61000-4-2,3,4,5,6,8,11, EN55024, EN61000-6-2 (EN50082-2), EN61204-3, heavy industry level, criteria A, EAC TP TC 020 |
MTBF |
486.2K hrs min. MIL-HDBK-217F (25ºC) |
DIMENSION |
32*125.2*102mm (W*H*D) |
PACKING |
0.51Kg; 28pcs/15.3Kg/1.22CUFT |
NOTE |
|
1. All parameters NOT specially mentioned are measured at 230VAC input, rated load and 25ºC of ambient temperature. 2. Ripple & noise are measured at 20MHz of bandwidth by using a 12" twisted pair-wire terminated with a 0.1uf & 47uf parallel capacitor. 3. Tolerance : includes set up tolerance, line regulation and load regulation. 4. The power supply is considered a component which will be installed into a final equipment. The final equipment must be re-confirmed that it still meets EMC directives. |