Din Rail Power Supplies |
OUTPUT |
|
Model |
NDR-480-12 |
NDR-480-24 |
NDR-480-48 |
DC Voltage |
12V |
24V |
48V |
Rated Current |
40A |
20A |
10A |
Current Range |
0-40A |
0-20A |
0-10A |
Rated Power |
480W |
480W |
480W |
Ripple & Noise |
100mVp-p |
200mVp-p |
400mVp-p |
Voltage Adj. Range |
13.5-16.5V |
24-28V |
48-53V |
Voltage Tolerance |
±2% |
±1% |
±1% |
Line regulation |
±0.5% |
±0.5% |
±0.5% |
Load regulation |
±1% |
±1% |
±1% |
Setup, Rise Time |
500ms,70ms/230VAC 500ms,70ms/115VAC at full load |
Hold Up Time |
36ms/230VAC 32ms/115VAC at full load |
INPUT |
|
Voltage Range |
88~132VAC/176~264VAC selected by switch 47~63Hz; 248~370VDC |
AC Current |
4.8A/115VAC 2.4A/230VAC |
Efficiency |
83% |
85% |
87% |
Inrush Current |
Cold start 20A/115V 35A/230V |
Leakage Current |
<3.5mA/240VAC |
Over Load |
105%~150% rated output power |
Protection type: Constant current limiting, recovers automatically after fault condition is removed |
Over Voltage |
15-16.5V |
29-33V |
58-65V |
Protection type: Shut down o/p voltage, re-power on to recover |
Over Temp. |
85ºC±5ºC(TSW1) |
90ºC±5ºC(TSW1) |
90ºC±5ºC(TSW1) |
Protection type: Shut down o/p voltage, recovers automatically after temperature goes down |
Working Temp., Humidity |
-10ºC~+60ºC; 20%~90% RH non-condensing |
Storage Temp., Humidity |
-20ºC~+85ºC; 10%~95%RH |
Vibration |
10~500Hz, 2G 10min./1cycle, period for 60min, each along X, Y, Z axes |
Withstand Voltage |
I/P-O/P: 3KVAC I/P-FG: 1.5KVAC O/P-FG: 0.5KVAC |
Isolation Resistance |
I/P-O/P, I/P-FG, O/P-FG: 100M Ohms / 500VDC/25ºC/70%RH |
Safety Standard |
Design refer to UL508,UL60950-1,TUV EN60950-1 |
EMC Standard |
Design refer to EN55011,EN55022,EN61000-3-2,-3,EN61000-4-2,3,4,5,6,8,11,EN55024,EN61000-6-2(EN50082-2), heavy industry level, criteria A |
Dimension |
85.5*125.2*128.5mmmm(L*W*H) |
Weight |
1.5Kg |
Packing |